माताटीला जल विद्युत केंद्र

Hydro Electric Project, Matatila

Installed capacity - 3 x 10.2 = 30.6MW

No. of units - 3

Sailent Features

Matatila Power Station is located in Lalitpur district (UP), 60 K.m. far from Jhansi City. Nearest Railway Station is Jhansi on the Delhi-Bombay route.

Power Station is situated at the left bank of river Betwa, which rises from Bhopal in the Vindhyan Plateau at an elevation of 1550ft, passes through granite rocks at a steep gradient, the river flows on outskirts of distt. Jhansi, forming boundary line of U.P. and M. P and thereafter it mostly flows in U.P., meeting the river Yamuna in Hamirpur Distt in U.P.

It is entirely a rain-fed river with very high discharge of water during rainy season and extremely low discharge during summers. The dam was constructed in year 1957 for irrigation purposes. Matatila Power House with three machines of 10.2 MW each on the existing dam was commissioned in 1965.

Hydrology

Catchment Area - 8000 Sq. Miles.

Reservoir Capacity at - 40000 M. Cu. Ft. Full level (R L 1012ft)

Climatic Data

The Climate of Matatila dam is very hot in summer season and some time temperature rises upto 50ºC during summer and very cold during winter season. There is monsoon rains in summer season only The climate is dry in rest of the year.

DAM

Masonary dam flanked by earthen embankments on either side.

Height 104.0 ft
Crest Length 1,394.0 ft
Crest Width 534.0 ft
Maximum Width at base 1,394 ft
Spillway gate 23 Nos
Size of gate 60'x23'
Type of gate Radial
Water Conducter System Through Penstock

DETAILS OF INTAKE STRUCTURE (Including type, number and size of gate)

Particulars Height Length Width Still Level
Intake gate 20' 11'-8" 1'-8" 942'
Stop Log gate 5' (5 Nos)
3'-8" (1 No.)
15'-6" 2' 942'
Draft Tube gate 14'-4" 9'-3" 1'-8"quot; 886'

Penstock

Type Cylindrical Steel Pipe
No. of Penstock 3
Dia 11'-3"
Length 210 ft

Two pipe lines of Jal Nigam are connected with penstock of Machines for drinking water supply to Jhansi city.

Building

Power station building is located at left bank of the Dm, Length of the building is 205 meters, Width - 76.5 meters, Height - 109 meters, Control room of power house is located at left side of the building.

. Type of Control Board - Relay logic type

. Type of protection board - Mechanical relay Type

. Type of recorder - Analogue Type

Above mentioned boards are installed in control room.

Head & Design Discharge

(1) Gross maximum head 102 ft
(2) Gross Minimum head 60 ft
(3) Discharge at Max. head 1659 Cusec.

Installed Capacity & Number of Units

(1) Installed Capacity 3x10.2 = 30.6 MW
(2) Number of Units 3 Nos

Turbine

(a) Type of Turbine Vertical Shaft Kaplan Turbine
(b) Output at max. head 16,500 BHP
(c) Discharge at Max. head 1655 Cusec
(d) Number of Runner blades 6 Nos
(e) Specific Speed 115.6
(f) Efficiency at full load 89.4%
(g) Guide vane 20 Nos
(h) Material Shaft Forged Steel
(i) Dia of Shaft 19.75"
(j) Max. Run away speed 675 rpm

RUNNER

(a) No. of Runner blades 06 Nos
(b) Material of blades 13 chromium cast steel
(c) Material of Runner boss Low magnetic steel
(d) Internal dia 98 ½"
(e) Velocity of Runner Unit 40.1 EPS

GOVERNOR

(a) Type Hitachi Cabinet type speed governor
(b) Range of adjustment of speed level 0.6
(c) Guaranteed Sensitivity 0.1%
(d) Closing time of guide vanes 7.2 Seconds
(e) Opening time of full gate 15 Seconds

Type of Generator & Excitation System

Generator
(a) Capacity 12000 KVA
(b) R.P.M. 250
(c) Full Load current 630 Amp. 3$
(d) Generating Voltage 11 KV
(e) No. of Poles 24
(f) Power factor 0.85
(g) Efficiency at full load 96.45%
(h) Insulation class 'B'
(i) Outer dia of stator 177"
(j) Generator air Gap 1"
(k) Field current 400 amp

Main Excitor

(a) Capacity 120KW
(b) Full load voltage 220V
(c) Ampere 546amp
(d) Exciting Voltage 110V
(e) Field Separate
(f) Insulation Class 'A'

Pilot Excitor

(a) Capacity 5 KW
(b) Full Load Voltage 110 v
(c) Ampere 45.5 Amp
(d) Field Compound
(e) Insulation Class 'A'

A.V.R

(a) Type Thyristor control Regulator type
(b) DC Control Voltage 110 V ± 5%

Details of The Tailrace

(a) Type Open Channel
(b) Intake crest length 60'
(c) Maximum level 913' (Normal)
(d) Minimum level 908
(e) Length 10 meter (Appx)
(f) Width 35 meter (Appx)
(g) Draft tube gate 06 Nos

Firm Power and Annual Energy Generation

(a) Firm power 9.56 MW
(b) Peaking Capacity during mansoon 30.6 MW
(c) Peaking capacity during summer 19.0 MW
(d) Firm output 81.65 MU
(e) Seasonal output 41.928 MU

Details of Switch Yard

(a) Size & Type Open
(b) Transmission voltage 66 KV and 11 KV
(c) No. of Bay 01
(d) Incomers 03
(e) Outgoing feeder 05

Name of Outgoing Feeder

(a) 66 KV Jhansi feeder 02 Nos (25 MVA each)
(b) 66 KV MP (Pichhore) feeder 01 No (5MW)
(c) 66 KV RORA feeder 01 No. (2MW)
(d) 66 KV Lalitpur feeder 01 No (5MVA) (Disconnected at present)

Name of Incomers

(a) No. of M/C 03 Nos.
(b) M/C load 10.2MW (each)

TRANSFORMER

Generating TIF - 03 Nos
(a) Capacity 12000KVA (Make- Toshiba)
(b) Volts 11/66KV
(c) Current 630/105 Amp
(d) Phase 3 $
(e) Vector symbol YD 11
(f) Type of cooling ON
(g) Impedance 7.68%
(h) Capacity of oil 2160 Gallons
(i) Weight of Oil 8.874 TONS
(j) Total Weight 34.1 TONS
(k) Tape Changer No load type (off load)

2MVA T/F (66/11KV) - 2 Nos

(a) Make Crompton & Parkinson
(b) Capacity 2000 KVA
(c) Volt 66/11 KV
(d) Current 17.5/105 amp
(e) Type of Cooling ON
(f) Impedance 7.51%
(g) Vector Symbol YD 11
(h) Weight of oil 4640 KG
(i) Oil Capacity 5470 Lit

UNIT AUXILIARY T/F - 03 Nos and station T/F - 02 Nos

(a) Make ECE
(b) Capacity 300 KVA
(c) Volts 11/0.4 KV
(d) Current 15.75 amp/432.8 amp
(e) Type of Cooling ON
(f) Impedance 4.7%
(g) Vector Symbol DY 11
(h) Oil Weight 650 Lit. /570 Kg

BREAKER - Make HEL Bhopal

(a) Type LG 3C/66 (Bulk oil type) 66 KV Breaker
(b) Voltage 66 KV
(c) Current Capacity 800 amp
(d) Breaking capacity 13.1KA, 3 Sec.
(e) Making capacity 33.4 KA
(f) Closing/Tripping Coil Voltage 110 V DC

For 66 KV MP (Pichhore) feeder Breaker - 01 No

(a) Type SF-6
(b) Voltage 66 KV
(c) Make ASEA
(d) Making Capacity 45 KA
(e) Breaking capacity 17.5 KA

SIZE OF SWITCH YARD

(a) Size of Switchyard 160' x 100'
(b) Size of Transformeryard 80' x 129'

Total Project Cost / Cost of Generation

(1). (a) Net cost of Generation (F.Y. 2000-01) - 17.28 Paise per Unit
      (b) Total Project cost - 416.009 Lacs

(2). Unit wise details of the machines as per name plate for both turbine and Generator:-

ACTUATOR GENERATOR

For 12000 KVA Actuator
RPM --250
MFG. No.-- 106464
Date-- 1963

DC Generator

RPM-250       Code- BSS RPM- 250       Code- BSS
Main Exciter Pilot Excitor
Kw- 120       Type- VFB       Form -SP Kw 5       Type-VB.       Form -K
Full Load Volt - 220       AMPS - 546 Full Load Volt - 110       AMPS- 45.5
Exciting Volts - 110       Rating - Cont Field - Comp       Rating - cont
Field - Separate Insulation       Class -A
Insulation       Class A Date 1963
Mfg no. -253166       Date -1963  

Alternating Current Generator

Type - VEFKW Form - RD Code BS:- 2613
KVA- 12000 RPM- 250 Phases -3 Poles- 24
Volts- 1000 AMPS- 630 Cycles- 50 PF 0-85
Main Ex.KW -120 Main Ex.Volt- 220 Main Ex. AMP- 443  
Mfg. No- 106461-1 Date -1963    
Pat No. -367954, 374078, 393066, 401955

Water Turbine

TYPE --VK FORM-- IRS  
EFFECTIVE HEAD DISCHARGE OUTPUT
MAX. 99 ft 1655 cfs 16500 HP
NOR. 85 ft 1655 cfs 14250 HP
MIN. 58 ft 1415 cfs 8000 HP
RPM 250 CODE BS353 DATE 1963
MFG NO. 141281-1 PAT NO. 205210  
TOKYO Hitachi Ltd JAPAN WP = T2453  

(5). General information in respect of Generation from the units and auxiliary consumption.

(a) Details of annual generation of last 6 years.

1996-97 - 131.172 MU
1997-98 - 157.997 MU
1998-99 - 132.805 MU
1999-00 - 160.909 MU
2000-01 - 138.083 MU
2001-02 - 140.203 MU

(b) Auxiliary consumption of the plant is approximately 0.2% of Generation.

(6). Schedule for annual maintenance

Annual maintenance of one M/C of Matatila Power House is being done each year for smooth Running of M/c's as per instructions issued earlier.

(7). R.L.A & L.E. of Matatila Power House is proposed to be carried out by M/S BHEL and order for the same has already been placed.

(8). An E.O.T crane of 80 ton capacity has already been installed in Power House for dismantaling and erection Works. A mechanical workshop having lathe M/C, Shapers, drill M/C & Welding M/C has also been installed in Matatila Power House.

Single Line Diagrame of Matatila Power House

matatila-hydro-diagram